Inuence of the process pressure to the switching point
1
2
3
4
12
(174,1)
38
(551,1)
25
(362,6)
51
(739,7)
64
(928,2)
10 (
25
/
64
")
8
(
5
/
16
")
6
(
15
/
6
4
")
4 (
5
/
3
2
")
2
(
5
/
64
")
-2
(
-5
/
64
")
-4
(
-5
/
3
2
")
-6
(
-15
/
64
")
-8
(
-5
/
16
")
-10
(
-25
/
64
")
0
Fig. 24: Inuence of the process pressure to the switching point
1 Shifting of the switching point in mm (in)
2 Process pressure in bar (psig)
3 Switching point at reference conditions (notch)
4 Tuning fork
Repeatability 0.1 mm (0.004 in)
Hysteresis approx. 2 mm (0.08 in) with vertical installation
Switching delay approx. 500 ms (on/o)
Frequency approx. 1200 Hz
Ambient conditions
Ambient temperature on the housing -40 +70 °C (-40 +158 °F)
Storage and transport temperature -40 +80 °C (-40 +176 °F)
Process conditions
Measured variable Limit level of liquids
Process pressure -1 64 bar/-100 6400 kPa (-14.5 928 psig)
depending on the process tting, e.g. ange (see
following diagrams)
Process temperature (thread or ange tem-
perature)
- LEVEL SWITCH 8112 of 316L/Hastelloy
C22 (2.4602)
-50 +150 °C (-58 +302 °F)
Process temperature (thread or ange tem-
perature) with temperature adapter (option)
- LEVEL SWITCH 8112 of 316L/Hastelloy
C22 (2.4602)
-50 +250 °C (-58 +482 °F)