5 Open the terminals with a screwdriver
6 Insert the wire ends into the open terminals according to the wiring
plan
7 Tighten the terminals with a screwdriver
8 Check the hold of the wires in the terminals by lightly pulling on
them
9 Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10 Screw the housing cover back on
The electrical connection is nished.
5.3 Wiring plan, single chamber housing
N
N A M U R
( I E C 6 0 9 4 7 - 5 - 6 )
m a x .
m i n .
S i m u l .
+ -
0,5 g / cm
3
0,7 g / cm
3
3
6
5
7
1
2
4
Fig. 10: Electronics and connection compartment, single chamber housing
1 Control lamp
2 DIL switch for characteristics reversal
3 DIL switch for sensitivity adjustment
4 Ground terminal
5 EMC lter element
6 Simulation key
7 Connection terminals
For connection of the amplier according to NAMUR (IEC 60947-5-6,
EN 50227). You can nd further information in the "Technical data".
Electro
nics and connec-
tion compartment
Wir
ing plan
18 LEVEL SWITCH 8112 with NAMUR output
5 Connecting to power supply
32052-EN-120418