- Pipe thread, cylindrical (DIN 3852-A) G¾ A, G1 A
- American pipe thread, conical
(ASME B1.20.1)
¾ NPT or 1 NPT
- Flanges DIN from DN 25, ANSI from 1"
- hygienic fittings Bolting DN 40 PN 40, Clamp 1 " DIN 32676
ISO 2852/316L, Clamp 1½" PN 10 DIN 32676
ISO 2852/316L, conus DN 25 PN 40, Tuchenhagen
Varivent DN 50 PN 10
Max. torque - process fitting
- Thread G¾ A, ¾ NPT 75 Nm (55 lbf ft)
- Thread G1 A, 1 NPT 100 Nm (73 lbf ft)
High voltage test (enamel) max. 5 KV
Gas-tight leadthrough (optional)
- Leakage rate < 10
-6
mbar l/s
- Pressure resistance PN 64
Output variable
Output Two-wire NAMUR output
Current consumption
- Falling characteristics ≥ 2.6 mA uncovered/≤ 0.6 mA covered
- rising characteristics ≤ 0.6 mA uncovered/≥ 2.6 mA covered
- Fault message ≤ 0.6 mA
Necessary processing system NAMUR processing system according to
IEC 60947-5-6 (EN 50227/DIN 19234)
Modes (NAMUR output adjustable to falling or rising characteristics)
- Min. rising characteristic curve (High current when
immersed)
- Max. falling characteristics (Low current when immersed)
Measuring accuracy
Deviation ± 1 mm (0.04 in)
LEVEL SWITCH 8112 • with NAMUR output 27
9 Supplement
32052-EN-120418