Página 1 - Operating Instructions

mxCONTROL Type 8620 Page 1 Type 8620 mxCONTROL Multifunction Water Treatment Controller Operating Instructions

Página 2 - Page 2

mxCONTROL Type 8620 Page 10 4 General Information 4.1 Scope of Delivery Verify immediately after receiving the shipment that the contents a

Página 3 - Contents

mxCONTROL Type 8620 Page 100 Output converter Normally, the module output CMD for the selection of actuators is only looped through the out

Página 4 - Page 4

mxCONTROL Type 8620 Page 101 Processdata and Data Logging Display-Presentation Displayed data Abbre-viation (menu) Full Screen Trend chart Lin

Página 5 - Page 5

mxCONTROL Type 8620 Page 102 Configuration (Code Level: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbreviatio

Página 6 - Presentation elements

mxCONTROL Type 8620 Page 103 14.3.3 On-/Off-Ratio Control (COND_CONTROL_RATIO) This module allows a simple On-/Off ratio control of the condu

Página 7 - 2 Intended Use

mxCONTROL Type 8620 Page 104 Pre-bleeding and "Biocide Dosing" Module Compare the section "Pre-bleeding and "Biocide Do

Página 8 - CAUTION!

mxCONTROL Type 8620 Page 105 Processdata and Data Logging Display-Presentation Displayed data Abbre-viation (menu) Full Screen Trend chart Lin

Página 9

mxCONTROL Type 8620 Page 106 14.3.4 PI-Ratio Control (COND_PI_RATIO) This module allows a simple PI ratio control of the conductivity with

Página 10 - 4 General Information

mxCONTROL Type 8620 Page 107 Maximum Output Timer (MOT) Compare the description of the Maximum Output Timer in section "Maximum Output Ti

Página 11 - 5 Abbreviations

mxCONTROL Type 8620 Page 108 Configuration (CodeLevel: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbreviation

Página 12 - Page 12

mxCONTROL Type 8620 Page 109 14.4 Corrosion Display (CORROSION-DISPLAY) The corrosion display indicates the corrosion rate measured by the co

Página 13 - Page 13

mxCONTROL Type 8620 Page 11 5 Abbreviations 5.1 Abbreviations in Software and Documentation Further abbreviations (Error messages) can be fo

Página 14 - Abbreviation Explanation

mxCONTROL Type 8620 Page 110 14.5 pH Controller Modules (PH_ACID_CAUS) and (PH_ACID_OR_CAUS) The pH control function is designed for P a

Página 15 - 5.2 Display of the units

mxCONTROL Type 8620 Page 111 Figure 49: Slope of the ramp In manual mode the set point according to the ramp function is set to the

Página 16 - Page 16

mxCONTROL Type 8620 Page 112 Output Override The output of this module is influenced at certain states (see Figure 51). Figure 51: Output o

Página 17 - 6 Technical Data

mxCONTROL Type 8620 Page 113 Processdata and Data Logging Display-Presentation Displayed data Abbre-viation (menu) Full Screen Trend chart Lin

Página 18 - Page 18

mxCONTROL Type 8620 Page 114 Configuration (CodeLevel: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbreviation

Página 19 - Page 19

mxCONTROL Type 8620 Page 115 14.5.2 pH Control (PH_ ACID_OR_CAUS) This module permits a pH-Control with Acids or Bases and with the optional

Página 20 - 6.2 Type Plate – Example

mxCONTROL Type 8620 Page 116 PVProportional Controller Output CMDSPModule - sense of action: normal DeadbandPVSPModule - sense of action: i

Página 21 - 6.3 Hardware Structure

mxCONTROL Type 8620 Page 117 The internal timer counting the period of the maximum control output will be reset if the control output is smal

Página 22 - 6.4 Module Overview

mxCONTROL Type 8620 Page 118 Configuration (Code Level: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbreviatio

Página 23 - 7 Installation

mxCONTROL Type 8620 Page 119 14.6 Dosing of oxygen absorption media 14.6.1 Flow and temperature-based dosing (O2_SCAV_CTRL_RATIO) This modul

Página 24 - 7.4 Electrical Connections

mxCONTROL Type 8620 Page 12 Abbreviation Explanation CORROSION_DISPLAY Corrosion Display Module Cut- Lower CutOff threshold (Module &quo

Página 25 - Electrical Connections

mxCONTROL Type 8620 Page 120 Oxygen concentration Since the relationship between temperature and dissolved oxygen is non-linear, the module

Página 26 - 7.5.1 Power Supply (PS)

mxCONTROL Type 8620 Page 121 Output Override The output of this module is influenced at certain states (see figure). AutomaticManualOperation

Página 27 - Page 27

mxCONTROL Type 8620 Page 122 Configuration (Code Level: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbrevia-ti

Página 28 - 8.1 Safety Notes

mxCONTROL Type 8620 Page 123 14.6.2 Process-value-proportional dosing (OPEN_PROP) This module calculates the control output proportionally to

Página 29 - 8.3 Operation Mode

mxCONTROL Type 8620 Page 124 Output Override The output of this module is influenced at certain states (see figure). AutomaticManualOperat

Página 30 - 8.4 Layout of Menu Screens

mxCONTROL Type 8620 Page 125 14.7 Chlorine / Redox Control (CL_ORP) The chlorine/redox control function is designed for P and PI control. Th

Página 31 - 9 Menu Structure

mxCONTROL Type 8620 Page 126 Output Override The output of this module is influenced at certain states (see figure). AutomaticManualOperati

Página 32 - Page 32

mxCONTROL Type 8620 Page 127 Processdata and Data Logging Display-Presentation Displayed data Abbre-viation (menu) Full Screen Trend chart Lin

Página 33 - 9.2 Setting Numeric Values

mxCONTROL Type 8620 Page 128 14.8 Batch Dosing (BATCH) The input signal for the batch controller is derived from one of the digital inputs

Página 34 - 10 Password Protection

mxCONTROL Type 8620 Page 129 ... When a dosing event occures, - Batch1 immediately doses for 10 minutes. - Batch2 waits 11 minutes, and d

Página 35 - Changing Passwords

mxCONTROL Type 8620 Page 13 Abbreviation Explanation PH_ACID_CAUS pH PI Module with selection of acid and caustic pump PH_ACID_OR_CAUS p

Página 36 - 11.1 Functional Overview

mxCONTROL Type 8620 Page 130 Parameter (CodeLevel: Operator) Parameter Abbrevia-tion (menu) Value range Default values (after successful do

Página 37 - 11.2.1 Download

mxCONTROL Type 8620 Page 131 14.9 Time scheduled Biocide Dosing (BIOCIDE_DOSING) The Biocide Dosing Module is designed for a fully automated

Página 38 - 11.2.2 Upload

mxCONTROL Type 8620 Page 132 Pre-bleed function: After the 14-day timer has started biocide dosing, it may be desirable to delay the execut

Página 39 - 11.3 Data Logging

mxCONTROL Type 8620 Page 133 The Figure 69 demonstrates the relationship between system water conductivity and biocide dosing. Delay Tm1Bleed

Página 40 - Datalog failed alarm

mxCONTROL Type 8620 Page 134 Output Override The output of this module is influenced at certain states (see the following figure).

Página 41

mxCONTROL Type 8620 Page 135 Parameter (CodeLevel: Operator) Parameter Abbrevia-tion (menu) Value range Default values (after successful downl

Página 42 - Page 42

mxCONTROL Type 8620 Page 136 Figure 71: Parameterizing the Biocide 14-Day Dosing Timer Configuration (CodeLevel: Specialist) Config

Página 43 - Page 43

mxCONTROL Type 8620 Page 137 14.10 Monitoring Process Values (MONITOR_PV) This module is designed for external monitoring of up to two proce

Página 44 - Page 44

mxCONTROL Type 8620 Page 138 Parameter (CodeLevel: Operator) No parameter available. Configuration (Code Level: Specialist) Configuration

Página 45 - 11.4.2 Operating Language

mxCONTROL Type 8620 Page 139 14.11 Dual Channel Totalizer (TOTALIZER) This module allows separate summarizing of total amount of flow from u

Página 46 - 11.5 Communication

mxCONTROL Type 8620 Page 14 Abbreviation Explanation YF Out fails (MOT is expired) YS Safety output value is active (due to input/sensor

Página 47 - Display of Ethernet state

mxCONTROL Type 8620 Page 140 Totalizer 101SystemSwitch0 01Flow Switch0 PV 1Totalizer 201SystemSwitch0 01Flow Switch0 PV 2System Switch over

Página 48 - Functionality

mxCONTROL Type 8620 Page 141 Configuration (Code Level: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbreviation (

Página 49 - Renotification

mxCONTROL Type 8620 Page 142 15 Alarm and Error Messages 15.1 Alarm function This function actuates the common alarm output whenever a con

Página 50

mxCONTROL Type 8620 Page 143 The alarm and warning limits for inputs can be changed in the configuration menu in the menu of the desired input

Página 51 - Ethernet event

mxCONTROL Type 8620 Page 144 15.2 Displaying (Input-) Alarms and different (Output-) States The input alarms and output states are display

Página 52 - Page 52

mxCONTROL Type 8620 Page 145 15.3 Error Messages and Warnings Most of the error messages and warnings are displayed as a short message for ap

Página 53 - Function overview

mxCONTROL Type 8620 Page 146 Warning or Error message Displayed as Displaying interval Cause Remedy CalibFault 4-20mA Out (Output state:

Página 54 - Display of current state

mxCONTROL Type 8620 Page 147 Warning or Error message Displayed as Displaying interval Cause Remedy XX = 01 … 08, 21, Y = 1: The cause is o

Página 55 - 12 Inputs

mxCONTROL Type 8620 Page 148 Warning or Error message Displayed as Displaying interval Cause Remedy Max.Value overflow short message on

Página 56 - 12.1.1 Binary Inputs

mxCONTROL Type 8620 Page 149 Warning or Error message Displayed as Displaying interval Cause Remedy SD-Card locked short message (duri

Página 57 - 12.1.2 Frequency Inputs

mxCONTROL Type 8620 Page 15 5.2 Display of the units Because of the limited display, there is not always sufficient room available for the de

Página 58 - Page 58

mxCONTROL Type 8620 Page 150 Warning or Error message Displayed as Displaying interval Cause Remedy SD: Error Open File short message

Página 59 - (Process Value) Alarm

mxCONTROL Type 8620 Page 151 Warning or Error message Displayed as Displaying interval Cause Remedy SMTP Error X Y short message once Com

Página 60 - Page 60

mxCONTROL Type 8620 Page 152 Warning or Error message Displayed as Displaying interval Cause Remedy User Calib failed permanent message

Página 61 - Page 61

mxCONTROL Type 8620 Page 153 16 Maintenance and troubleshooting 16.1 Safety Notes DANGER! Danger from electrical voltage! Reaching into the

Página 62 - 12.2 Analog Inputs

mxCONTROL Type 8620 Page 154 17 Spare parts CAUTION! Danger from wrong accessories and wrong spare parts! Wrong accessories and unsuitab

Página 63 - Scaling

mxCONTROL Type 8620 Page 155 21 Appendices 21.1 Project (for example "BW 06") 21.1.1 Input/Output Assignment – project "BW 0

Página 64 - Special input function

mxCONTROL Type 8620 Page 156 21.2 Power Supply of Actuators/Sensors 21.2.1 Power Supply out of the mxCONTROL 21.2.2 Separate Power Su

Página 65 - User Calibration

mxCONTROL Type 8620 Page 157 21.3 Hardware Version 1 21.3.1 PIN Assignment for Power Supply Level (Power Supply) Pin No. Signal Function

Página 66 - Page 66

mxCONTROL Type 8620 Page 158 21.3.2 PIN Assignment for Low Voltage Level (Instrumentation Supply) PIN no. Signal Function Designation i

Página 67 - (Default: Yes)

mxCONTROL Type 8620 Page 159 21.3.3 Connection Examples for Inputs and Outputs Digital-/Frequency Inputs XXXXXXXXXXXXmxCONTROL 8620Power Supp

Página 68 - rw rw Offset

mxCONTROL Type 8620 Page 16 Display max. 3 characters Display max. 6 characters Display of the unit selection as well as data logging uni

Página 69 - 12.2.2 Pt100 Inputs

mxCONTROL Type 8620 Page 160 Pt100 Inputs Example: Connection of a Pt100-sensor to AnalogIn 1 Analog Outputs 4…20 mA Example: Connection

Página 70 - Page 70

mxCONTROL Type 8620 Page 161 Relay Outputs Examples: Connection of a device working with mains voltage (1): to the „break contact“ of Rel

Página 71

mxCONTROL Type 8620 Page 162 21.4 Hardware version 2 21.4.1 PIN assignment for power supply level (power supply) Pin No. Signal Funct

Página 72 - 13 Outputs

mxCONTROL Type 8620 Page 163 21.4.2 PIN Assignment for Low Voltage Level (Instrumentation Supply) PIN no. Signal Function Designation in t

Página 73 - 13.1.2 Relay as PFM Output

mxCONTROL Type 8620 Page 164 21.4.3 Connection Examples for Inputs and Outputs Digital-/Frequency Inputs Input is configured as: - Poten

Página 74 - 13.1.3 Relay as PWM Output

mxCONTROL Type 8620 Page 165 Analog Inputs 4…20 mA Examples: (1): Connection of a 2-wire-sensor to AnalogIn 1 (2): Connection of a 3-wire-s

Página 75 - Page 75

mxCONTROL Type 8620 Page 166 Analog Outputs 4…20 mA Example: Connection of a device with analog output 4…20 mA to 4…20mA-Ausgang 1 (if n

Página 76 - Page 76

mxCONTROL Type 8620 Page 167 Relay Outputs Examples: Connection of a device working with mains voltage (1): to the „break contact“ of Rel

Página 77 - Page 77

mxCONTROL Type 8620 Page 168 21.5 Main Menu Structure – Menu Tree (Example for Project "BW 06T") 21.5.1 Processdata – Inputs –

Página 78

mxCONTROL Type 8620 Page 169 21.5.2 Processdata – Cond Control

Página 79 - Page 79

mxCONTROL Type 8620 Page 17 6 Technical Data 6.1 Technical Specifications These operating instructions are valid from Firmware revision: C

Página 80 - 14 Controller Modules

mxCONTROL Type 8620 Page 170 21.5.3 Configuration of Inputs

Página 81 - Page 81

mxCONTROL Type 8620 Page 171 21.5.4 Configuration of the Codes ProcessdataBW 06ParameterConfigurationSystem settingsENTER3from Item 4to Item

Página 82 - Configuration

mxCONTROL Type 8620 Page 172 21.5.5 System Settings - Current Firmware ID-No. and Revision- Current Eeprom Revision- Number of cold device

Página 83

mxCONTROL Type 8620 Page 173 21.5.6 Up-/Download - Download Config-FileDownloadEXITSD-Card...EXIT: CancelFile foundDownloadEXITSD-Card...

Página 84 - Page 84

mxCONTROL Type 8620 Page 174 21.5.7 Up-/Download – Upload

Página 85 - Kx = PV / PV2

mxCONTROL Type 8620 Page 175 21.5.8 Data Logging / Calibration / Clock ConfigurationBW 06TSystem settingsUp-/DownloadData LoggingENTER6EXITt

Página 86

mxCONTROL Type 8620 Page 176 21.6 Data Logging File – Example #HEADER DatalogFile Rev A.00 Source DEVICE

Página 87 - PID Controller

mxCONTROL Type 8620 Page 177 Legend State PV (English) State CMD (English) Line 1: (User defined) names of Control Fu

Página 88 - )( PVSPKp

mxCONTROL Type 8620 Page 18 Internal Equipment – Inputs Inputs Hardware version 1: 4 Analog inputs (4 … 20 mA or Pt100; software-

Página 89

mxCONTROL Type 8620 Page 19 Communication SD card SD card capacity: minimum 64 MB, maximum 2 GB, formatted with FAT16 file system Up-/downlo

Página 90 - Page 90

mxCONTROL Type 8620 Page 2 We reserve the right to make changes without notice! © 2009 - 2010 Bürkert Wer

Página 91

mxCONTROL Type 8620 Page 20 CE mark applicable tests resulting in CE mark UL/CSA (for UL/CSA approved versions) conform to Std. UL61010-1

Página 92

mxCONTROL Type 8620 Page 21 6.3 Hardware Structure This simplified block diagram shows the main hardware components of „Type 8620 mxCONTROL“

Página 93 - Page 93

mxCONTROL Type 8620 Page 22 6.4 Module Overview This table shows the available standard modules which can be combined specifically for th

Página 94 - Ratio Control

mxCONTROL Type 8620 Page 23 7 Installation 7.1 Safety Notes DANGER! Danger from electrical voltage! Reaching into the system presents an acu

Página 95 - COND_CONTROL

mxCONTROL Type 8620 Page 24 7.3 Mechanical Installation Direct sunlight will reduce the viewing contrast at the display – although it is h

Página 96

mxCONTROL Type 8620 Page 25 Dimensioning of fuses, line safety switches, overcurrent protection devices Pay attention to correct design of the

Página 97

mxCONTROL Type 8620 Page 26 Figure 5: Cable with cable end sleeves → Then guide the prepared cable through the cable gland opening

Página 98

mxCONTROL Type 8620 Page 27 7.5.2 Instrumentation Supply (IS) Connect the cables as shown in the PIN tables in the appendix (21.3.2 and 21.4.

Página 99 - 14.3.2 PI-Control (COND_PI)

mxCONTROL Type 8620 Page 28 8 Description of Human-Machine Interface 8.1 Safety Notes WARNING! Danger from improper operation! Improper

Página 100 - Maximum Output Timer (MOT)

mxCONTROL Type 8620 Page 29 8.3 Operation Mode 8.3.1 Automatic & Manual Mode Key A/M key with yellow LED The A/M key switches between

Página 101 - Processdata and Data Logging

mxCONTROL Type 8620 Page 3 Contents CONTENTS 3 1 THE OPERATING INSTRUCTIONS 6 2 INTENDED USE 7 2.1 Restrictions 7 2.2 Anticipated mis

Página 102 - Page 102

mxCONTROL Type 8620 Page 30 8.4 Layout of Menu Screens Running bar directly below the upper horizontal screen border, running from the l

Página 103 - Switching Hysteresis [µS/cm]

mxCONTROL Type 8620 Page 31 9 Menu Structure 9.1 Principle of Menu Tree Structure A welcome message appears in the display after switching o

Página 104 - On/Off-Controller

mxCONTROL Type 8620 Page 32 A similar structure is given for all “projects”. The main menu items contain submenus as exemplary listed belo

Página 105

mxCONTROL Type 8620 Page 33 9.2 Setting Numeric Values Parameters, i.e. their numeric values can be changed within predefined ranges. They ar

Página 106 - PI Controller

mxCONTROL Type 8620 Page 34 10 Password Protection Three authorization levels (CodeLevel) are provided for the operation of „Type 8620 mxCO

Página 107

mxCONTROL Type 8620 Page 35 Changing Passwords → Choose the main menu item “Configuration”, enter with “ENTER” → Enter the specialist passw

Página 108 - Page 108

mxCONTROL Type 8620 Page 36 11 General Software Concept and Functions 11.1 Functional Overview The „Type 8620 mxCONTROL“ is a configurabl

Página 109 - Acid Stop Limit (ASL)

mxCONTROL Type 8620 Page 37 Most modules have a spezial ”Output Override“-Function (override the original output value) in order to react to s

Página 110 - (PH_ACID_OR_CAUS)

mxCONTROL Type 8620 Page 38 → Select the desired configuration file "XXX.cfg" for download into the „Type 8620 mxCONTROL“, pre

Página 111

mxCONTROL Type 8620 Page 39 Stopping/cancelling of the upload process – by pressing key „EXIT“ - makes the uploaded file incomplete and it c

Página 112

mxCONTROL Type 8620 Page 4 11.4 Configuration and Parameterization 45 11.4.1 Preface about Configuration/Parameterisation 45 11.4.2 Op

Página 113

mxCONTROL Type 8620 Page 40 The layout of the data logging file, the abbreviations and the coding used in the header are shown in an examp

Página 114 - Page 114

mxCONTROL Type 8620 Page 41 Parameter (CodeLevel: Operator) Parameter Access via Datalog-menu Access via XML-Param.-File Abbre-viation (menu)

Página 115

mxCONTROL Type 8620 Page 42 11.3.1 Selection of SD card size for Data Logging purposes The size required for one process data sample depe

Página 116

mxCONTROL Type 8620 Page 43 Estimation for a blank SD card, formatted with FAT16 file system: Required SD card size [MByte] 0,9][MBytememory

Página 117

mxCONTROL Type 8620 Page 44 Changing sample time: → Select „Tsample“, press key “INPUT” → Input a new value for „Tsample“ (via keys „+“

Página 118 - Page 118

mxCONTROL Type 8620 Page 45 11.4 Configuration and Parameterization 11.4.1 Preface about Configuration/Parameterisation The configuration (C

Página 119 - (O2_SCAV_CTRL_RATIO)

mxCONTROL Type 8620 Page 46 11.5 Communication 11.5.1 USB Device access via USB allows putting the “Type 8620 mxCONTROL” easily into servi

Página 120 - Control output limitation

mxCONTROL Type 8620 Page 47 Features Feature Operational Speed 10 / 100 Mbps (auto negotiation) IP address assignment Static (recommended

Página 121

mxCONTROL Type 8620 Page 48 Email notification Requirements A mail server is required, that • supports SMTP (Simple Mail Transfer Protoco

Página 122 - Page 122

mxCONTROL Type 8620 Page 49 Up to 4 emails can be sent with one server connection. There is a 5 second mail server reconnection delay, in orde

Página 123 - Dosing control

mxCONTROL Type 8620 Page 5 15 ALARM AND ERROR MESSAGES 142 15.1 Alarm function 142 15.2 Displaying (Input-) Alarms and different (Output-

Página 124

mxCONTROL Type 8620 Page 50 Email 1 – Alarm renotification Email 2 – Warning renotification Remote device access via PC-Tool Requireme

Página 125

mxCONTROL Type 8620 Page 51 Datalogging The datalog file of devices with Ethernet option contains 2 additional columns: “Ethernet state” and

Página 126

mxCONTROL Type 8620 Page 52 Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbrevia-tion (menu) Value range Default values (af

Página 127

mxCONTROL Type 8620 Page 53 Function overview PC Tool menu item Explanation Connection One connection possible at one time. Connection … E

Página 128 - 14.8 Batch Dosing (BATCH)

mxCONTROL Type 8620 Page 54 Display of current state Do not change parameters / values, when remote upload or download is active. The fol

Página 129

mxCONTROL Type 8620 Page 55 12 Inputs Depending on the hardware version, the „Type 8620 mxCONTROL“ has digital and analog inputs which can be

Página 130 - Page 130

mxCONTROL Type 8620 Page 56 12.1.1 Binary Inputs Binary inputs are usually used to detect special outer conditions, which shall have an ef

Página 131 - (BIOCIDE_DOSING)

mxCONTROL Type 8620 Page 57 The alarm information is displayed in the menu Processdata\Inputs as an icon similar to the input alarms of freque

Página 132 - Page 132

mxCONTROL Type 8620 Page 58 The K-Factor specifies the amount of pulses per volume unit. The K-Factor can specified in different units - pl

Página 133 - Page 133

mxCONTROL Type 8620 Page 59 Unit Group Measuring units (*)Miscellaneous ppm, V, mA, Pulse, Hz, %, no unit? Chemical Analysis µS/cm, mS/cm,

Página 134

mxCONTROL Type 8620 Page 6 1 The operating instructions WARNING! The operating instructions must be read and understood. Read the opera

Página 135 - Page 135

mxCONTROL Type 8620 Page 60 Figure 15: Alarm/warning - switching hysteresis For displaying and data logging purposes ther

Página 136 - Page 136

mxCONTROL Type 8620 Page 61 Configuration (CodeLevel: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbre-viation (m

Página 137

mxCONTROL Type 8620 Page 62 12.1.3 Pulse Counter Inputs The pulse counter inputs, for example, can be used in combination with the Batch D

Página 138 - Page 138

mxCONTROL Type 8620 Page 63 Scaling ScalDir = Rise: Scal+ High scaling value, assigned to the maximum current (20 mA) Scal- Low scal

Página 139 - Override

mxCONTROL Type 8620 Page 64 Special input function There is special root extraction function available, e.g. for adapting special flow sens

Página 140

mxCONTROL Type 8620 Page 65 For displaying and data logging purposes there are adjustable upper and lower warning limits and a separate warni

Página 141 - Page 141

mxCONTROL Type 8620 Page 66 Calibration Mode “1-point” This calibration mode can be used for the calibration of 4-20mA input signals from

Página 142 - 15 Alarm and Error Messages

mxCONTROL Type 8620 Page 67 → Hold the current PV during the calibration procedure: Yes or No (Default: Yes). Hold-Function – for calibra

Página 143 - Page 143

mxCONTROL Type 8620 Page 68 Configuration (CodeLevel: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbre-viation

Página 144 - (Output-) States

mxCONTROL Type 8620 Page 69 12.2.2 Pt100 Inputs Figure 19: Pt100 Input A/D-Conversion The enabled analog Pt100 inputs are sampled every 50

Página 145 - Page 145

mxCONTROL Type 8620 Page 7 2 Intended Use WARNING! Hazards to persons, equipment in the vicinity and the environment may result when not us

Página 146 - specific data of control

mxCONTROL Type 8620 Page 70 Procedure of determining the Correction value 1. Place the Pt100 sensor and another calibrated temperature s

Página 147 - Page 147

mxCONTROL Type 8620 Page 71 Low Pass Filter Please refer to the description of the low pass filter in section 12.2.1. (Process Value) Alarm

Página 148 - Page 148

mxCONTROL Type 8620 Page 72 13 Outputs The „Type 8620 mxCONTROL“ has 5 relay outputs by default. Depending on the hardware version, the „T

Página 149 - Page 149

mxCONTROL Type 8620 Page 73 13.1.1 Relay as Binary Output (On/Off) Time tController Output100%(on)0%(off)Time tRelay Output(break cont

Página 150 - Page 150

mxCONTROL Type 8620 Page 74 13.1.3 Relay as PWM Output Time tT1T2T2 T2Relay dropoutRelay activatedRelay Output (break contact)with constan

Página 151 - Page 151

mxCONTROL Type 8620 Page 75 13.2 Analog 4...20 mA Outputs (Option) The control output of the connected module output is converted to a 4…20 m

Página 152 - Page 152

mxCONTROL Type 8620 Page 76 → Select „Offset“, press key “INPUT” (Æ the device outputs now a current of 4 mA at the 4-20mA output X) →

Página 153 - 16.3 Malfunctions

mxCONTROL Type 8620 Page 77 13.3 Transistor Outputs (Option) Technical details of the transistor outputs are described in chapter 6.1 “Technic

Página 154 - 20 Disposal

mxCONTROL Type 8620 Page 78 control output is changed only be this max. permitted value. The maximum manipulating speed can be configured s

Página 155 - Instrumentation

mxCONTROL Type 8620 Page 79 13.3.5 Configuration (Code Level: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbre-v

Página 156 - (24 V DC)

mxCONTROL Type 8620 Page 8 3 General Safety Instructions These safety instructions do not take any • Incidents and occurrences into acco

Página 157 - 21.3 Hardware Version 1

mxCONTROL Type 8620 Page 80 14 Controller Modules Functions, containing a control or displaying module, can be enabled or disabled directly

Página 158 - (Instrumentation Supply)

mxCONTROL Type 8620 Page 81 14.1.3 System Switch override function (Specialist level) The "System Switch Override" function (functi

Página 159

mxCONTROL Type 8620 Page 82 Configuration Configuration System Switch Access via Cfg.-menu Access via XML-Cfg.-File Abbre-viation (menu)) V

Página 160 - Transistor Outputs

mxCONTROL Type 8620 Page 83 Potentialfree binary input as "Flow Switch" logical value input voltage Input signal: Not inverted (In

Página 161 - Relay Outputs

mxCONTROL Type 8620 Page 84 14.1.5 Maximum Output Timer (MOT) Some control modules contain a maximum output timer in order to detect wheth

Página 162 - 21.4 Hardware version 2

mxCONTROL Type 8620 Page 85 14.2 General PID controller (COMMON_PID) The general PID controller module COMMON_PID is provided for the proce

Página 163

mxCONTROL Type 8620 Page 86 The set point value of the subordinate controller must therefore be configured as "int.casc" and conn

Página 164 - Bin. out

mxCONTROL Type 8620 Page 87 Set value limiter (SP Limit) The set point limiter is used to limit the adjustable set point through a minimum an

Página 165 - Analog Inputs 4…20 mA

mxCONTROL Type 8620 Page 88 Gain/amplification factor Kp: The behaviour of the controller's P-part is influenced by the gain/amplifica

Página 166

mxCONTROL Type 8620 Page 89 Module Sense of Action: The module sense of action (controller sense of action) is reversible. The module sense of

Página 167

mxCONTROL Type 8620 Page 9 CAUTION! Hardware and Software modifications and changes For safety reasons unauthorised modifications and changes

Página 168 - Page 168

mxCONTROL Type 8620 Page 90 • charact 1 • For simple control output limitation • charact 2 • For control output limitation with scali

Página 169 - Page 169

mxCONTROL Type 8620 Page 91 Figure 33: Control output limitation with control range (COMMON_PID). Output Override The output

Página 170 - Page 170

mxCONTROL Type 8620 Page 92 Processdata and Data Logging Display-Presentation Displayed data Abbre-viation (menu) Full Screen Trend chart L

Página 171

mxCONTROL Type 8620 Page 93 Configuration (CodeLevel: Specialist) Configuration Access via Cfg.-menu Access via XML-Cfg.-File Abbrevia-tion (m

Página 172 - 21.5.5 System Settings

mxCONTROL Type 8620 Page 94 14.3 Conductivity Control Modules Several control strategies are implemented for a closed loop control of syst

Página 173 - Page 173

mxCONTROL Type 8620 Page 95 14.3.1 On-/Off-Control (COND_CONTROL) This module allows a simple On-/Off Control of the conductivity with the op

Página 174 - Page 174

mxCONTROL Type 8620 Page 96 On/Off-Controller The On/Off-Controller is used to control simple on/off-outputs, e.g. a bleed valve. The On/Of

Página 175

mxCONTROL Type 8620 Page 97 Maximum Output Timer (MOT) This function monitors the controller output in automatic mode. If the controller outpu

Página 176 - Page 176

mxCONTROL Type 8620 Page 98 Processdata and Data Logging Display-Presentation Displayed data Abbre-viation (menu) Full Screen Trend chart L

Página 177 - Page 177

mxCONTROL Type 8620 Page 99 14.3.2 PI-Control (COND_PI) This module permits a Proportional Integral (PI)-Control of the conductivity with an o