0911 - 17
english
6 FACTORY SETTING
PA
1
Description Range Default PE
2
SET Set-value LS1 + US1 0 Pr1
HY1 Switch hysterisis 1
dependent on measurement
range
-1 Pr1
LS1 Lowest set-value 1
Lower measurement range +
SET1
min Pr2
US1 Largest set-value 1
Upper measurement range +
SET1
max Pr2
S1C Control effect Output 1 in = inverse; dir = direct in Pr2
Ac Delay time for the relay 0...250 sec 0 Pr2
on
Minimum switch-on time
for a relay
0...250 sec 0 Pr2
ono
Minimum waiting time
between two consecutive
activations of the same
load
0...120 min 0 Pr2
ALC
Alarm limits are absolute
values or related to the
set-value
rE = relative; Ab = absolute rE Pr2
ALL
Lower Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range
10 Pr2
ALU
Upper Alarm Limit
(ALC = rE; ALC = Ab)
dependent on measurement
range
10 Pr2
ALH
Switch hysterisis for
temperature alarms
dependent on measurement
range
2Pr2
ALd
Alarm delay time during
the operation
0...999 min 15 Pr2
dAO
Alarm delay time after
commissioning
0...23.5 h 1.3 Pr2
So1 Output 1 for sensor error oFF = open; on = closed oFF Pr2
tbA
Alarm relay can be
acknowledged
no; yES yES Pr2
AS
Polarity of the Alarm
relay
CL...oP oP Pr2
LCI
3
Lower analog display
value
depending on sensor var. Pr2
1
Parameter
2
Programming level
3
Only for devices with voltage and current input